Page view 6
5
State
V
boost
V
float
14.4V
13.8V
PB-1000-12
28.8V
27.6V
57.6V
55.2V
PB-1000-24 PB-1000 -48
Figure 6.2 3 stage ch arging curve
Constant
Current
60A 34.7A 17.4A
100%
10%
Explanation for 3 stag es charging curve
(0)Initial stage (battery analysis):
(1)Stage 1 (constant current):
(2)Stage 2 (constant voltage):
(3)Stage 3 (Flo at voltage):
Check battery voltage level to se e if it is within the normal range, w hether o r not
a ba ttery is conn ected, or if th e battery is alre ady full and furth er charging is no t
requ ired.
A constant current is provided so the battery can be quickly charged to 2.4V per cell.
A constant voltage of 2.4V per cell is provided until the charging current naturally
A float voltage of 2.3V per cell is provided so that the battery can maintain full charge.
tapers down to 10% then move on to stage 3.
Charge Current
Start
Charge Voltage
boost
float
V
V
Constant Current
stage 1 stage 2 stage 3
Constant Voltage
Battery Full
Orange Green
Color of LED
6.3 8 s tage charging (flick switch to "8" stage)
8 stage charging provides optimized charge to lead acid battery. It also prolongs
battery life and increase storage capacit y. Some of the ma in advantages are as
below:
Advantage of pulse stage: Use pulse current to revive aged battery.
Advantage of recondition stage: Allow full charge of battery.
*For applications that u tilize the charger (PB-1000) t o charge batteries and su pply.
System po wer simultaneously(e.g. UPS system), pl ease select "3 sta ge" chargin g
for the best use of the c harger.